Thursday, December 19, 2013

PROCEDURE FOR MAINTENANCE OF BATTERY



THE EXACT NATURE OF WORK THAT ARE TO BE CARRIED OUT AS FOLLOWS:


   A)    Batteries are to be cleaned properly, each individual cell is to be cleaned thoroughly along with racks and cabinet.



   B)    Check and clean the battery vents.



C)    The battery leads inter cell connections etc are to be checked for tightness and treated (Greasing) check all connections if necessary replace them.



D)   Check electrolyte level and if required, top up with fresh electrolyte up to correct level(Consider the manufacturer recommendations)



E)     Measure the density using Hydrometer and note down the result.



F)     Check the in line voltage of each cell with properly scaled in line voltmeter and record reading.

Note: If the result as above (Item No:”E&F”) shows that any of the cells is weak, they are to be replaced with new ones.



G)   Clean the battery compartment and the battery Charger unit,check all the Circuits and components of the battery charger and ensure correct operation of charger in all conditions i.e. at high rate and low rate,check all meters and indication lamps for proper operation,replace the burnt out items as necessary,after the maintenance,the charger is to be put on low rate charging and should not be left on high rate charging.


          

H)    Check whether the DC supply reaches the switchgear panel or not,if any interruption is noticed,replace the wiring between the battery unit and the switch gear panel.

Wednesday, December 18, 2013

SYSTEM OF INSTRUMENT EARTHING




Instrument earthing system shall consist of the following earth type:

Electrical earthing (also called dirty earthing or Protective Earthing  (PE))



     Instrument earthing (also called Reference Earth (RE))



     Intrinsically safe earthing


Electrical earthing is used to protect the power system, electrical equipment, and personnel from electric shock.

 How to do an Electrical Earthing?

      Armor of field instrument cable shall be terminated at cable gland.



      Armor of single and multi core cable going to junction box shall be terminated at cable gland. If the junction box made from metal, then it only needs to connect the earth stud bolt to the nearest steel structure. If the junction box made from non metal, the earth stud bolt will be located at the metal gland plates which have direct contact with the cable gland.



      Armor of single and multi core cable going inside or outside marshalling and system cabinet shall be terminated and connected to a bus bar inside the cabinet. Each bus bar inside the cabinet will be connected to a grounding dispatcher by 35 mmsq cable (usually green – yellow stripped). This grounding dispatcher will collect all connection from individual bus bar and then connect it to a general electrical earth loop (to structure steel) by a 70 mmsq cable. In general used, the earth bus bar is made from copper and has 1 ½” width and ¼” height.


2.       Instrument earth

     The general principle of instrument earth is all individual shields (screen) and overall shield (screen) of single or multi pair cable shall be isolated from electrical earthing and terminated at different bus bar. This instrument earth usually also called reference earth since it serve the reference point of the instrument loop (ground of internal electric circuit inside the instrument).



      Individual shield (drain wire) of single pair cable shall be terminated at earth or ground terminal block inside the instrument enclosure.



      Individual shield from analog single pair cable going inside the junction box shall be terminated to terminal block. Individual shield from digital single pair cable going inside the junction box shall be terminated to terminal block and jump out each other then connect it to bus bar.



     Individual shield from multi pair cable going inside the junction box shall be also terminated to terminal block match with the individual shield from single pair cable.



      Overall shield from multi pair analog cable going inside the junction box shall be terminated to terminal block or bus bar (overall shield at analog cable doesn’t have a pair with the shield from single pair cable). Overall shield from multi pair digital cable going inside the junction box shall be terminated to bus bar.



      All individual and overall shields (screen) from multi pair cable shall be terminated into respective instrument earth bus bar at marshalling cabinet.



      Instrument bus bar will be connected to grounding dispatcher by 25 mmsq green-yellow stripped cable. From grounding dispatcher, it will be connected to main instrument earth loop by 70 mmsq green-yellow stripped cable.


3.       Intrinsically safe earthing

      Isolation and termination of IS field cable shields (screen) at field devices, junction boxes and marshalling cabinets shall be done in the same manner as for instrument earth explained above. However the overall shield (screen) of multi pair cable for IS signals goes to marshalling cabinet shall be terminated individually and connected to its IS bus bar. The individual shield (screen) of this cable will be terminated directly to a galvanic isolator and then connected to the respective IS bus bar.



The following maximum resistance limits shall be achieved after the instrument earthing system installed. This resistance is minimized as much as possible so the ub-normal current can be safely grounded at steel structure.



     Between instrument earth bus bars and grounding dispatcher not greater than 0.5 ohm.



     Between electrical equipment frame and nearest local stud earth on structural steel not greater than 1 ohm.



     Between intrinsically safe installation and grounding dispatcher not greater than 0.5 ohm.





Tuesday, December 17, 2013

FIRE AND GAS DETECTION PHILOSOPHY




Fire Detection

In general, the fire detection system shall have the following objectives:

  -          To detect fire in very early stage of it’s form.

  -          To alert operator at control room and give them the location.

  -          To alert any personnel at location of the fire event so that they are aware and could take any necessary action.

-          To activate the fire fighting equipment.

Based on these, there are four main types of the fire detection devices (fire detector):

-          Smoke detector.

-          Heat detector.

-          Flame detector (detect the UV or IR radiated by fire).

-          Multi-detector (combination of smoke and heat).

Each detector has a unique purpose and suitability for a specific application. Thus the detector type should be selected based on the safety (loss prevention) study. It will depend on the speed of response required, consequences to facility, and the area of the fire events.

Smoke detectors

The most used smoke detectors are ionization type and photoelectric type. The ionization type utilizes a constant current that produced by electrode from an ionization of some isotope. Any particle that goes through the chamber and interrupt the ionization will make a reduction of constant current. Thus alarm will be activated. The photoelectric type utilizes a scattered light from smoke particles to measure the smoke present. Any particles that interrupt the light line (it will be scattered) will cause the detector activated.

The smoke detector (both ionization and photoelectric type) are very sensitive and shall not be used at dirty environments, smoky atmosphere, and open areas where there is an unpredictable air flows. For example, smoke detector shall not be used at kitchen, mechanical workshop, etc.

Another type of smoke detectors that most used at offshore oil & gas industries are High Sensitive Smoke Detectors. This detector usually placed on the very critical areas such as cable ducting, control room, and electrical room. This detector take a sample of each sample location by an air-sampling tubes and then draw the sample to a centralized detector which analyze any small present of smoke. It will allow the system to give very fast and earliest alert to an operator of fire event (event it still on the smoke forming stage).

Flame Detectors

Flame detectors are categorized as fast response devices. It senses the flame on a line of sight. A fire consists of three part, smoke, heat, and flame. This detector is utilizing at application when flame is the first part of fire that formed, such as a hydrocarbon leak area.

There are three major types of flame detectors:

-          Ultra-Violet (UV) Flame Detectors

-          Infrared (IR) Flame Detectors

-          Combination of UV and IR Flame Detectors

Ultra-Violet (UV) Flame Detectors

UV type flame detectors are detectors that sense the UV light emitted from a flame. It’s sensitive to a sun UV light, welding arcs, x-rays, and lightning. Therefore the use of UV flame detector is limited on the closed area where the disturbance from sun, lightning etc is absent such as a turbine compressor closure, turbine generator closure etc.

UV flame detectors are also shouldn’t use to detect fire that have heavy smoke (i.e. crude oil) or fires that doesn’t have visible flame (i.e. alcohol etc).

Infrared (IR) Flame Detectors

Infrared flame detectors are detectors that sense the hot light (infrared) emitted by a CO2 product of flame. Its very reliable than UV flame detector because of more immune to UV light, welding arcs, etc. It can be used in open areas or closed areas. The infrared flame detectors signal shall be filtered from hot human body and set it to insensitive to hot body.

Combination of UV & IR Flame Detectors

UV/IR Flame Detectors use both UV and IR sensor to sense a flame. It should be selectable to be UV only or IR only or both sensors active. It should be detect any flame whether indoor or outdoor applications. If both UV and IR sensor are active, it will only send alarm signal when both of it sense a fire. It will reduce the false alarm that caused by using UV only or IR only.

Heat or Thermal Detectors

Heat detector is slower device compare to smoke detector and flame detector. This detector utilize a heat sensitive element (usually are thermistor) to sense the heat. It will activate only after the fire reaches some significant stage to radiate its heat energy and sensed by the heat sensitive of heat detectors. Even though this detector has slow response to fire but it’s very suitable for application that prone to alarm false if we use smoke or flame detectors such as kitchen area, workshop, laboratory room, smoking area etc.

There are three types of heat detectors:

-          Fixed type.

-          Rate of rise type.

-          Fusible plugs.

Fixed heat detectors

A fixed heat detector is a detector that set at a fixed temperature set point. Once the ambient temperatures (caused by a fire) reach the set point, the detectors will send an alarm signal. As a standard, the fixed heat detectors set point is 77 Celsius. Fixed heat detectors are very suitable for application that has a swings temperature on it i.e. kitchen, workshop, laboratory room etc.

Rate of rise heat detectors

Rate of rise heat detectors is a detector that senses the rate of rise in the ambient temperature. It’s very sensitive heat detectors and can cause a false alarm at a room having swing temperature. Normally it will activate when the heat rate of rise is between 12 Fahrenheit or 15 Fahrenheit. It’s suitable to use at smoking room, warehouse etc. It’s also suitable to use at room that doesn’t have a high air flow that can cause a smoke detector slow to response such as storage room or warehouse.

Fusible Plugs

Fusible plugs are a metal cylinder that has a sealed metal with low melting point. It is connected to a pneumatic tubing loop. When the ambient temperatures reach the melting point of the seal metal, then the seal will broke and causing a pneumatic air leak through it. This leak will be detected by a pressure switch and it will initiate an alarm that activates a very large capacity valve to operate. This large capacity valves (called deluge valve) will spout a fire water to extinguish fires. The fusible plug is designed to protect a closed vessel from a fire. When a closed vessel exposed to a fire, it can causing a dangerous rise in internal pressure of vessels and causing a blow up. Therefore usually it put out around a closed vessel.

Wednesday, December 11, 2013

EARTHING

          
        

WHAT IS EARTHING?

The main reason for doing earthing in electrical network is for the safety. When all metallic parts in electrical equipments are grounded then if the insulation inside the equipments fails there are no dangerous voltages present in the equipment case. If the live wire touches the grounded case then the circuit is effectively shorted and fuse will immediately blow. When the fuse is blown then the dangerous voltages are away.

PURPOSE OF EARTHING

SAFETY FOR HUMAN/EQUIPMENTS/BUILDINGS:-

·        To save human life from danger of electrical shock or death by blowing a fuse i.e.

·        To protect buildings, machinery & appliances under fault conditions

·        To  provide an alternative path for the fault current to flow so that it will not endanger the user

·        To ensure that all exposed conductive parts do not reach a dangerous potential.

·        To provide stable platform for operation of sensitive electronic equipments   i.e.

·        To provide safe path to dissipate lightning and short circuit currents.

·        To maintain the voltage at any part of an electrical system at a known value so as to prevent over current or excessive voltage on the appliances or equipment.


VOLTAGE STABILIZATION:-

There are many sources of electricity. Every transformer can be considered a separate source. If there were not a common reference point for all these voltage sources it would be extremely difficult to calculate their relationships to each other. The earth is the most omnipresent conductive surface, and so it was adopted in the very beginnings of electrical distribution systems as a nearly universal standard for all electric systems.

OVER VOLTAGE PROTECTION:-

Lightning, line surges or unintentional contact with higher voltage lines can cause dangerously high voltages to the electrical distribution system. Earthing provides an alternative path around the electrical system to minimize damages in the System.

DIFFERENT METHOD OF EARTHING

PLATE TYPE EARTHING:-
·        Generally for plate type earthing normal Practice is to use

·        Cast iron plate of size 600 mm x600 mm x12 mm. OR

·        Galvanized iron plate of size 600 mm x600 mm x6 mm. OR

·        Copper plate of size 600 mm * 600 mm * 3.15 mm

·        Plate  burred at the depth of 8 feet in the vertical position and GI strip of size 50 mmx6 mm bolted with the plate is brought up to the ground level.

·        These types of earth pit are generally filled with alternate layer of charcoal & salt up to 4 feet from the bottom of the pit.

PIPE TYPE EARTHING:-
·         For Pipe type earthing normal practice is to use

·         GI pipe [C-class] of 75 mm diameter, 10 feet long welded with 75 mm diameter GI flange having 6 numbers of holes for the connection of earth wires and inserted in ground by auger method.

·         These types of earth pit are generally filled with alternate layer of charcoal & salt or earth reactivation compound.

DESCRIBE THE METHOD OF CONSTRUCTION OF EARTH PIT
·         Excavation on earth for a normal earth Pit size is 1.5M X 1.5M X 3.0 M.

·         Use 500 mm X 500 mm X 10 mm GI Plate or Bigger Size for more Contact of Earth and reduce Earth Resistance.

·          Make a mixture of Wood Coal Powder Salt & Sand all in equal part

·          Wood Coal Powder use as good conductor of electricity, anti corrosive, rust proves for GI Plate for long life.

·         The purpose of coal and salt is to keep wet the soil permanently.

·         The salt percolates and coal absorbs water keeping the soil wet.

·         Care should always be taken by watering the earth pits in summer so that the pit soil will be wet.

·         Coal is made of carbon which is good conductor minimizing the earth resistant.

·         Salt use as electrolyte to form conductivity between GI Plate Coal and Earth with humidity.

·         Sand has used to form porosity to cycle water & humidity around the mixture.

·         Put GI Plate (EARTH PLATE) of size 500 mm X 500 mm X 10 mm in the mid of mixture.

·         Use Double GI Strip size 30 mm X 10 mm to connect GI Plate to System Earthling.

·          It will be better to use GI Pipe of size 2.5 diameter with a Flange on the top of GI Pipe to cover GI Strip from EARTH PLATE to Top Flange.

·         Cover Top of GI pipe with a T joint to avoid jamming of pipe with dust & mud and also use water time to time through this pipe to bottom of earth plate.

·         Maintain less than one Ohm Resistance from EARTH PIT conductor to a distance of 15 Meters around the EARTH PIT with another conductor dip on the Earth at least 500 mm deep.

·         Check Voltage between Earth Pit conductors to Neutral of Mains Supply 220V AC 50 Hz it should be less than 2.0 Volts.

THE FOLLOWING FACTORS ARE EFFECTING THE EARTH PIT

SOIL RESISTIVITY:-
·        It is the resistance of soil to the passage of electric current. The earth resistance value (ohmic value) of an earth pit depends on soil resistivity. It is the resistance of the soil to the passage of electric current.

·        It varies from soil to soil. It depends on the physical composition of the soil, moisture, dissolved salts, grain size and distribution, seasonal variation, current magnitude etc.

·        In depends on the composition of soil, Moisture content, Dissolved salts, grain size and its distribution, seasonal variation, current magnitude.

MOISTURE:-
·         Moisture has a great influence on resistivity value of soil. The resistivity of a soil can be determined by the quantity of water held by the soil and resistivity of the water itself. Conduction of electricity in soil is through water.

·         The resistance drops quickly to a more or less steady minimum value of about 15% moisture. And further increase of moisture level in soil will have little effect on soil resistivity. In many locations water table goes down in dry weather conditions. Therefore, it is essential to pour water in and around the earth pit to maintain moisture in dry weather conditions. Moisture significantly influences soil resistivity

SOIL CONDITION:-
·         Different soil conditions give different soil resistivity. Most of the soils are very poor conductors of electricity when they are completely dry. Soil resistivity is measured in ohm-meters or ohm-cm.

·         Soil plays a significant role in determining the performance of Electrode.

·         Soil with low resistivity is highly corrosive. If soil is dry then soil resistivity value will be very high.

·         If soil resistivity is high, earth resistance of electrode will also be high.

DISSOLVED SALT:-
·        Pure water is poor conductor of electricity.

·        Resistivity of soil depends on resistivity of water which in turn depends on the amount and nature of salts dissolved in it.

·        Small quantity of salts in water reduces soil resistivity by 80%. common salt is most effective in improving conductivity of soil. But it corrodes metal and hence discouraged.
  
PHYSICAL COMPOSITION:-
·        Different soil composition gives different average resistivity. Based on the type of soil, the resistivity of clay soil may be in the range of 4 – 150 ohm-meter, whereas for rocky or gravel soils, the same may be well above 1000 ohm-meter.

WEATHER CONDITION:-
 ·         Increase or decrease of moisture content determines the increase or decrease of soil resistivity.

·         Thus in dry whether resistivity will be very high and in monsoon months the resistivity will be low.

LOCATION OF EARTH PIT:-
·         The location also contributes to resistivity to a great extent. In a sloping landscape, or in a land with made up of soil, or areas which are hilly, rocky or sandy, water runs off and in dry weather conditions water table goes down very fast. In such situation Back fill Compound will not be able to attract moisture, as the soil around the pit would be dry. The earth pits located in such areas must be watered at frequent intervals, particularly during dry weather conditions.

·         Though back fill compound retains moisture under normal conditions, it gives off moisture during dry weather to the dry soil around the electrode, and in the process loses moisture over a period of time. Therefore, choose a site that is naturally not well drained.

EFFECT OF CURRENT MAGNITUDE:-
·         Soil resistivity in the vicinity of ground electrode may be affected by current flowing from the electrode into the surrounding soil.

·         The thermal characteristics and the moisture content of the soil will determine if a current of a given magnitude and duration will cause significant drying and thus increase the effect of soil resistivity
  
 EFFECT OF GRAIN SIZE AND DISTRIBUTION:-
·         Grain size, its distribution and closeness of packing are also contributory factors, since they control the manner in which the moisture is held in the soil.

·         Effect of seasonal variation on soil resistivity: Increase or decrease of moisture content in soil determines decrease or increase of soil resistivity. Thus in dry weather resistivity will be very high and during rainy season the resistivity will be low.

 OBSTRUCTIONS:-
·        The soil may look good on the surface but there may be obstructions below a few feet like virgin rock. In that event resistivity will be affected. Obstructions like concrete structure near about the pits will affect resistivity. If the earth pits are close by, the resistance value will be high.

AREA AVAILABLE:-
·        Single electrode rod or strip or plate will not achieve the desired resistance alone.

·         If a number of electrodes could be installed and interconnected the desired resistance could be achieved. The distance between the electrodes must be equal to the driven depth to avoid overlapping of area of influence. Each electrode, therefore, must be outside the resistance area of the other.

CURRENT MAGNITUDE:-
·        A current of significant magnitude and duration will cause significant drying condition in soil and thus increase the soil resistivity.

MEASUREMENT OF EARTH RESISTANCE BY USING EARTH TESTER OR EARTH MEGGER:-
 ·         For measuring soil resistivity Earth Tester is used. It is also called the “MEGGER”.

·         It has a voltage source, a meter to measure Resistance in ohms, switches to change instrument range, Wires to connect terminal to Earth Electrode and Spikes.

·         It is measured by using Four Terminal Earth Tester Instrument. The terminals are connected by wires as in illustration.

·         P=Potential Spike and C=Current Spike. The distance between the spikes may be 1M, 2M, 5M, 10M, 35M, and 50M.

·         All spikes are equidistant and in straight line to maintain electrical continuity.  Take measurement in different directions.

·         Soil resistivity =2πLR.

·         R= Value of Earth resistance in ohm.

·         Distance between the spikes in cm.

·         π  =  3.14

·         P = Earth resistivity ohm-cm.

·         Earth resistance value is directly proportional to Soil resistivity value

THREE POINT METHOD OF MEASURING EARTH RESISTANCE:-
·         In this method earth tester terminal C1 & P1 are shorted to each other and connected to the earth electrode (pipe) under test.

·         Terminals P2 & C2 are connected to the two separate spikes driven in earth.  These two spikes are kept in same line at the distance of 25 meters and 50 meters due to which there will not be mutual interference in the field of individual spikes.

·         If we rotate generator handle with specific speed we get directly earth resistance on scale.

·         Spike length in the earth should not be more than 1/20th distance between two spikes.

·         Resistance must be verified by increasing or decreasing the distance between the tester electrode and the spikes by 5 meter. Normally, the length of wires should be 10 and 15 Meter or in proportion of 62% of ‘D’.

·         Suppose, the distance of Current Spike from Earth Electrode D = 60 ft, Then, distance of Potential Spike would be 62 % of D = 0.62D i.e.  0.62 x 60 ft = 37 ft.

FOUR POINT METHOD OF MEASURING EARTH RESISTANCE:-
·        In this method 4 spikes are driven in earth in same line at the equal distance.  Outer two spikes are connected to C1 & C2 terminals of earth tester.  Similarly inner two spikes are connected to P1 & P2 terminals.  Now if we rotate generator handle with specific speed, we get earth resistance value of that place.

·        In this method error due to polarization effect is eliminated and earth tester can be operated directly on A.C.

PIPE EARTHING VS PLATE EARTHING:-
 ·         Suppose Copper Plate having of size 1.2m x 1.2m x 3.15mm thick. soil resistivity of 100 ohm-m,

·         The resistance of Plate electrode to earth (R)=( r/A)X under root(π/A) = (100/2.88)X(3.14/2.88)=36.27 ohm

·         Now, consider a GI Pipe Electrode of 50 mm Diameter and 3 m Long. soil resistivity of 100 Ohm-m,

·         The resistance of Pipe electrode to earth (R) = (100r/2πL) X loge (4L/d) = (100X100/2X3.14X300) X loge (4X300/5) =29.09 Ohm.

·         From the above calculation the GI Pipe electrode offers a much lesser resistance than even a copper plate electrode.

·         As per IS 3043 Pipe, rod or strip has a much lower resistance than a plate of equal surface area.

GI EARTHING VS COPPER EARTHING:-
·         As per IS 3043, the resistance of Plate electrode to earth (R) = (r/A) X under root(P/A).

·         Where r = Resistivity of Soil Ohm-meter.

·         A=Area of Earthing Plate m3.

·         The resistance of Pipe electrode to earth (R) = (100r/2πL) X loge (4L/d).

·         Where L= Length of Pipe/Rod in cm

·         d=Diameter of Pipe/Rod in cm.

·         The resistivity of the soil and the physical dimensions of the electrode play important role of resistance of Rod with earth.

·         The material resistivity is not considered important role in earth resistivity.

·         Any material of given dimensions would offer the same resistance to earth. Except the sizing and number of the earthing conductor or the protective conductor.

LENGTH OF PIPE ELECTRODE AND EARTH PIT:-
·         The resistance to earth of a pipe or plate electrode reduces rapidly within the first few feet from ground (mostly 2 to 3 meter) but after that soil resistivity is mostly uniform.

·        After about 4 meter depth, there is no appreciable change in resistance to earth of the electrode. Except a number of rods in parallel are to be preferred to a single long rod.

AMOUNT OF SALT AND CHARCOAL (MORE THAN 8KG):-
·         To reduce soil resistivity, it is necessary to dissolve in the moisture particle in the Soil.

·         Some substance like Salt/Charcoal is highly conductive in water solution but the additive substance would reduce the resistivity of the soil, only when it is dissolved in the moisture in the soil after that additional quantity does not serve the Purpose.

·         5% moisture in Salt reduces earth resistivity rapidly and further increase in salt content will give a very little decrease in soil resistivity.

·         The salt content is expressed in percent by weight of the moisture content in the soil. Considering 1M3 of Soil, the moisture content at 10 percent will be about 144 kg. (10 percent of 1440 kg). The salt content shall be 5% of this (i.e.) 5% of 144kg, that is, about 7.2kg.

AMOUNT OF WATER POURING:-
·          Moisture content is one of the controlling factors of earth resistivity.

·         Above 20 % of moisture content, the resistivity is very little affected. But below 20% the resistivity increases rapidly with the decrease in moisture content.

·         If the moisture content is already above 20% there is no point in adding quantity of water into the earth pit, except perhaps wasting an important and scarce national resource like water.

LENGTH VS DIAMETER OF EARTH ELECTRODE:-
·         Apart from considerations of mechanical strength, there is little advantage to be gained from increasing the earth electrode diameter with the object in mind of increasing surface area in contact with the soil.

·         The usual practice is to select a diameter of earth electrode, which will have enough strength to enable it to be driven into the particular soil conditions without bending or splitting. Large diameter electrode may be more difficult to drive than smaller diameter electrode.

·         The depth to which an earth electrode is driven has much more influence on its electrical resistance characteristics than has its diameter.

MAXIMUM ALLOWABLE EARTH RESISTANCE:-
·         Major power station= 0.5 Ohm.

·         Major Sub-stations= 1.0 Ohm

·         Minor Sub-station = 2 Ohm

·         Neutral Bushing. =2 Ohm

·         Service connection = 4 Ohm

·         Medium Voltage Network =2 Ohm

·         L.T.Lightening Arrestor= 4 Ohm

·         L.T.Pole= 5 Ohm

·         H.T.Pole =10 Ohm

·         Tower =20-30 Ohm

METHOD OF MINIMIZING EARTH RESISTANCE:-
·         Remove Oxidation on joints and joints should be tightened.

·         Poured sufficient water in earth electrode.

·         Used bigger size of Earth Electrode.

·         Electrodes should be connected in parallel.

·         Earth pit of more depth & width- breadth should be made.