BEARING TEMPERATURE MEASUREMENT



1.what approximately is the bearing high temperature alarm and shutdown setting?

High speed bearings are protected against high temperatures. The high temperature alarm and shutdown instrument are generally set at 95degee C and 105degee C (refer to the station drawings for the exact settings/parameters).

2.What types of primary elements are used to measure the compressor bearing temperature? Give example with the equipment name.

At lower range of temperature ‘RTD’ (resistance temperature detector)is preferred to thermo-couples.

On dresser gas compressors: PT 100-RTD is used for measuring the journal and thrust bearing temperature.

On solar gas compressors: ‘k’ type thermo-couple is used for measuring the journal and thrust bearing temperature.

3.What maybe the reasons, if a compressor bearing temperature increases?

The following are the possible for compressor bearing temperature rise:

Defective bearing

Low lube oil supply pressure

Aged lube oil

Excessive compressor load

Dirty lube oil cooler

Lube oil cooler fan running at low speed

Defective thermostatic valve in the lube oil to cooler line

4.which of the two-‘resistance and thermo-couple’- is recommended for measuring a bearing temperature?

Resistance Temperature Detector- RTD is preferred over thermo-couple for measuring the bearing temperature. RTD is more accurate and linear in measuring temperature between the range  -200degee C to +200degee C.