Frequency of
Maintenance.-Molded case circuit breakers are designed to require little or no
routine maintenance throughout their normal lifetime. Therefore, the need for
preventive maintenance will vary depending on operating conditions. As an
accumulation of dust on the latch surfaces may affect the operation of the
breaker, molded case circuit breakers should be exercised at least once per
year. Routine trip testing should be performed every 3 to 5 years.
Routine
Maintenance test.-Routine maintenance tests enable personnel to determine if
breakers are able to perform their basic circuit protective functions. The
following tests may be performed during routine maintenance and are aimed at
assuring that the breakers are functionally Operable.
The following tests are to be made only on breakers and equipment that are
deenergized.
Insulation
resistance test.- A megohmmeter may be used to make tests between phases of
opposite polarity and from current-carrying parts of the circuit breaker to
ground.A test should also be made between the line and load terminals with the
breaker in the open position. Load and line conductors should be disconnected
from the breaker under insulation resistance tests to prevent test measurements
from also showing resistance of the attached circuit. RĂ©sistance values below 1
megohm are considered unsafe and the breaker should be inspected for possible
contamination on its surfaces.
Millivolt
drop test.- A millivolt drop test can disclose several abnormal conditions
inside a breaker such as eroded contacts, contaminated contacts, or loose
internal connections. The millivolt drop test should be made at a nominal
direct-current voltage at 50 amperes or 100 amperes for large breakers, and at or
below rating for smaller breakers. The millivolt drop is compared against
manufacturer's data for the breaker being tested.
Connections
test.- The connections to the circuit breaker should be inspected to determine
that a good joint is present and that overheating is not occurring. If
overheating is indicated by discoloration or signs of arcing, the connections
should be removed and the connecting surfaces cleaned.
Overload
tripping test.- The proper action of the overload tripping components of the circuit
breaker can be verified by applying 300 percent of the breaker rated continuous
current to each pole. The significant part of this test is the automatic
opening of the circuit breaker and not tripping times as these can be greatly
affected by ambient conditions and test conditions.
Mechanical operation.- The mechanical
operation of the breaker should be checked by turning the breaker on and off
several times.
No comments:
Post a Comment