MCC – MOTOR CONTROL
CENTRES:
MCC is a panel where all motor starters of particular are
assembled in one single cabinet. The parts of MCCs are cable chamber, start
compartment, bus bar chamber and an incoming feeder. The starter compartment
can be rack out type or fixed one.
PCC – POWER CONTROL
CENTRES:
PCC is a panel where power is being distributed to different
M<CCs, DB s and large motors. The parts of PCC are an incoming feeder and
outgoing feeder of different current ratings according to the connected load Normally
LT PCCs will be having OCBs or VCBs.
DB – DISTRIBUTION
BOARD:
Normally all DBs will be having fuse distribution. DBs used for
lighting will be having MCBs.
BUS – COUPLER:
Where two different bus sections connected through an breaker (ACB or VCB or OCB)
so that both bus section supply can have an alternative feeding arrangement.
EARTH SWITCH:
Where
the connected equipment transformer, motor or bus section can be earthed during
maintenance. This will provide perfect safety to the person working. If earth
switch is not there, that equipment has to earthed by using earth rod.
VCB – VACUUM CIRCUIT
BREAKER:
Vacuum is the dielectric used in the breakers.
Advantage: Non
flammable, non poisonous medium
Sealed interrupter, sealed for life
No maintenance is required for interrupter
Very long switch life
Suitable foe repeated switching
Used for high voltages from 3.3 KV to 11 KV
Self life vacuum interrupter is about 15 to 20 years
MCB Miniature
Circuit Breaker:
This isused for small loads such as lighting
MCCB MOULDED CASE
CIRCUIT BREAKER:
This is normally used for electronic controls. This can
avoid short circuit current very fast. They are replacing fuses.
ACB AIR CIRCUIT BREAKER:
Where air used for ARC
extinction normally used for low voltage switch gear.
OIL CIRCUIT BREAKER:
In these types of
breaker transformer oil is used as quenching medium. Now – a – days VCB is
replacing OCB as OCB requires maintenance and oil is easily inflammable.
BOCB – Bulk oil
circuit breaker
MOCB – Minimum
oil circuit breaker
In BOCB all three phase contacts assemble in a single tank.
In MOCB all three phase contacts assembled in three
different tanks.
SF- 6 Breaker – Sulphur Hexa Fluoride Breaker:
Where SF6 used
as a dielectric and arc quenching medium. Used for high voltage from 33KV to
760KV. SF6 is an inert gas.
Maintenance requirement of SF6 breakers are very much less
due to long contact life and inert operating medium.
Cost of the circuit breaker is less if cumulative
maintenance cost is also considered.
SF6 CB
is explosion proof, hence safe.
Normally
SF6 gas pressure is 5 kg / cm2
At 5
kg / cm2 the gas becomes liquid at 4°C
Mostly
all SF6 breakers use pressurized air for tripping.
HRC FUSE – HIGH RUPTURING CAPACITY CARTRIDGE
FUSE:
This fuse consists of a ceramic body having metal caps to which are
welded fuse-able silver or bimetallic current carrying elements. The body
surrounding the elements is completely packed with non inflammable power or
other special material like Quartz sand.
HRC fuses are used from
low voltage to up to 33 KV with short circuit capacities of about 8760 Amps at
that voltage. Normally HRC Fuse offers inverse time characteristic; if the
fault current is light the fusing time will be less.
P.T. – PONTENTIALTRANSFORMER:
Voltage transformer or potential
transformers are used foe measurement and protection. They may be either single
phase or 3 phases. In case of HT systems this transformer stepping down the
voltage for measuring and protection as high voltage cannot directly be used
for this purpose. The raring will normally be in VA (Volt Ampere) and this will
be around 200VA.
C.T. CURRENT TRANSFORMERS:
These are used for reducing /
stepping down A. C. current from higher value to lower value for measurement /
protection.
The rating of C. T. will be in VA Volt Ampere and that will
be between 10 VA to 30 VA.
Both P. T. & C. T. used for the following
For Measuring – Voltage, current, KVA,
KW, frequency, P. F. (cosѲ).
For protection – Over current, earth fault, differential,
reverse power, etc. Normally CT’s are mentioned as 10 P 10.
10P Accuracy class
percentage 3%
10 Composite
error 10%
CT secondary never be opened circuited. An important aspect in CT operation is the voltage appearing across open circuited secondary. Normal voltage 15 / 5 = 3 V. If by mistake secondary is open circuited the voltage across the secondary rises to some kilovolts. The increased voltage is because the following flux increases due to reduced back EMF in the secondary (as 0 current in the secondary)
Due to the high voltage in the secondary core of the C. T.
and Primary gets overheated and finally bursts off. Voltage are induced in the
secondary by electromagnetic induction. The peak value may rise several
kilovolts in the secondary. This may cause danger to personnel working on
secondary side. Therefore C. T. secondary should never be disconnected.
TRIP CIRCUIT HEALTHY
INDICATION
For knowing the trip circuit health a lamp connected in
series with the trip coil of breaker / lockout relay, the connection shown in
the diagram.
As the bulb resistance is higher than the trip coil, the
drop across the lamp will be higher than the trip coil, so bulb only glows.
ALARM ANNOUNCIATION
PANEL
Normally Alarm Annunciation panels will be window type
visual and audible bell or speaker.
When any one of the alarm initiated visual window lighting
will blink with audible sound. When accepted the audible alarm will stop. The
visual alarm can be resettled only after the fault clears away.
Each window will be connected to individual equipments
where announciation is required. The visual window will be around 50 to 100.
No comments:
Post a Comment